- Application Note -
Security Enhancements
Sequence of Operation
System Sequence of Events
Objective Equipment List
¨ Apex Destiny 6100 control panel,
rev. 8.05 or greater
¨ Apex RK36 or RKLCD keypad
¨ System Sensor Relay, A77-716B
¨ Four-Wire Smoke Detector
- Smoke Detector Power Supervision -
Provide supervision for
the smoke detector power
supply.
If power is lost to the smoke detector,
zone 1 will open and cause the system
to show a zone trouble. The system
will also begin to beep at the keypad
speaker and continue to beep until the
status key is pressed.
1) When power is interrupted to the smoke detector, power is also interrupted to the smoke
supervision relay. This will cause the relay to return to its normally open de-energized
state and remove the zone supervision resistor from zone input terminals 1 and C.
2) The system will now show a zone trouble and beep at the keypad speaker until the Status
button is pressed.
Four-Wire Smoke Detector
Apex Technical Support 800-272-7937
Option 1
Page 1-1