Sequence of Operation
System Sequence of Events
Objective Equipment List
¨ Apex Destiny 6100 control panel,
rev. 8.05 or greater
¨ Apex Temperature Sensor, TS16
¨ Enerzone Thermostat
AC, Gas/Electric: E3 300x1 1 heat/1cool
Heat Pump: E3 450x1 2 heat/1cool
- HVAC Temperature Control - Enerzone Thermostat -
Home/Away Temperature Setpoints
Provide temperature control with
independent heating and cool-
ing setpoints selected automati-
cally for the Home and Away
arming modes.
When the system is disarmed or armed to Home the temperature is maintained by the Enerzone
thermostat at the Day heating/cooling setpoints. When armed to Away the temperature is main-
tained by the Enerzone thermostat at the Night mode heating/cooling setpoints. All setpoints can
be changed at the thermostat. The TS16 temperature sensor allows the system to speak tem-
perature to the inside speakers and local/remote phone. It can also be programmed for high and
low alarm setpoints.
1) Arming the system to Away sends an ON command to Control Channel 1 energizing the on-
board relay and interrupting the connection between the thermostats CLK1 and CLK2 termi-
nals.
2) After one second, the system sends an OFF command to channel 1 to restore the
connection between CLK1 and CLK2 and place the thermostat in the Night(Away) mode.
3) Disarming the system or arming the system to Home sends an ON command to Control
Channel 2 energizing Auxiliary Output pin 1 and providing a ground signal to activate Zone 16.
Zone 16 sends an OFF command to Control Channel 33 deenergizing the on-board relay
and restoring the connection between CLK1 and CLK2.
4) After one second, the system sends an OFF command to Control Channel 2 deenergizing
Auxiliary Output pin1 and removing the ground signal to restore Zone 16. Zone 16 sends an
ON command to Control Channel 33 energizing the on-board relay to interrupt the connec-
tion between CLK1 and CLK2 and place the thermostat in the Day (Home) mode.
Apex Technical Support 800-272-7937
Option 1
Page 3-1
- Application Note -
Energy Management